Insulation thickness calculator

The calculator needs JavaScript. The worked example, formula and figures below show exactly how it works, so you can do the sum yourself. A guide, not advice. Check your supplier's or maker's figures before ordering.

Short answer

Worked example

Worked example inputs
You enterValue
ElementWall
The workNew element in an existing home (e.g. an extension)
Where the home isEngland
The other layers, inside to outsideBrick: material Brick (outer leaf), thickness 103 mm, thermal conductivity λ 0.77 W/mK, studs or joists run through this layer No; Aircrete block: material Aircrete block, thickness 100 mm, thermal conductivity λ 0.15 W/mK, studs or joists run through this layer No; Plaster: material Gypsum plaster, thickness 13 mm, thermal conductivity λ 0.57 W/mK, studs or joists run through this layer No
λ of the insulation you'll use0.022 W/mK
The insulation goes between studs or joistsNo
Target U-value0.18 W/m²K
Thickness you can buy at or above the answer120 mm
Inside surface resistance Rsi0.13 m²K/W
Outside surface resistance Rse0.04 m²K/W

Insulation: at least 100.4 mm

Worked example results
ResultValue
Minimum insulation thickness100.4 mm
Target U-value0.18 W/m²K
U-value with the thickness you'll buy0.155 W/m²K
U-value without the insulation1.007 W/m²K
Show the working
  1. Target: 0.18 W/m²K (your figure)
  2. Without the insulation: R = 0.993 m²K/W, U = 1.007 W/m²K
  3. Thickness: 0.022 × (1 ÷ 0.18 − 0.993) = 100.4 mm
  4. With 120 mm: U = 0.155 W/m²K

How it works

  1. Resistance of the other layers R_other = Rsi + Σ d/λ + Rse
  2. Thickness d = λ_insulation × (1 ÷ target U − R_other)
  3. When the insulation sits between studs or joists, the thickness is found by trying values until the combined-method U-value (BS EN ISO 6946) equals the target
  4. Then buy the next thickness up and check its U-value

Corrections for air gaps, wall ties and fixings (ΔU) aren't included: allow a little extra or ask the maker for a full calculation.

Our default (adjustable)

These are typical planning figures and our own allowances, not facts about your product. Change any of them in the calculator to match your bag, pack or tin.

FigureOur default (adjustable)KindSource
Inside surface resistance Rsi: Wall0.13 m²K/WOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Inside surface resistance for a wall (horizontal heat flow) as used in brief v2 I1 test UV1 (BS EN ISO 6946). Researcher to cite the clause.
Outside surface resistance Rse: Wall0.04 m²K/WOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Outside surface resistance for a wall as used in brief v2 I1 test UV1 (BS EN ISO 6946). Researcher to cite the clause.
Inside surface resistance Rsi: RoofEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rsi by element (BS EN ISO 6946), upward heat flow. Not stated in the brief; Researcher to fill.
Outside surface resistance Rse: RoofEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rse by element (BS EN ISO 6946). Not stated for roofs in the brief; Researcher to fill.
Inside surface resistance Rsi: FloorEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rsi by element (BS EN ISO 6946), downward heat flow. Not stated in the brief; Researcher to fill.
Outside surface resistance Rse: FloorEnter from the bag, pack or tinOur assumption
Not yet checked against the source
Our choice: change it to suit your job
Brief v2 I1: Rse by element (BS EN ISO 6946). Not stated for floors in the brief; Researcher to fill (ground floors are treated differently, BS EN ISO 13370).

Regulations and standards

  • Approved Document L 2021 Vol 1, Table 4.2 (new elements) and Table 4.3 (renovated elements), England
  • BS EN ISO 6946 (U-value method)

Explained: Approved Document L (conservation of fuel and power), BS EN ISO 6946 (U-values).

Our Part L figures are for England. Wales, Scotland and Northern Ireland set their own limits, which we're still adding.

Reference tables this calculator reads
TableClauseNationsStatus
Thermal conductivity (λ) of common materialsBS EN ISO 10456 design values / maker data sheets (Researcher to cite per row)UK-wide0/12 values entered
Not yet checked against the source
Part L limiting U-values by nation, element and workApproved Document L 2021 Vol 1 (England); Wales, Scotland and Northern Ireland equivalents (Researcher)UK-wide3/36 values entered
Not yet checked against the source

FAQs